3094A

ControlBus™, Coax RG-11, #14 Sol BCCS, FPE Ins, QUAD AL Shld, PVC Jkt, CMR

...
Coax RG-11 14AWG (Solid) Bare Copper Covered Steel, Foam PE Insulation, Overall Duobond® II+ Aluminum Braid(60%)+Duofoil®+Aluminum Braid(40%) Shield, PVC Outer Jacket, CMR
Request Sample Get Product Alerts
Specifications
Product Overview

Suitable Applications

harsh environment, factory automation, ControlNet™, Modbus II, Industrial Coax, Belden ControlNet cables provide maximum signal integrity and run length exceeding the high-speed, time-critical requirements necessary for ControlNet factory floor applications

Construction Details

RG Type

11

Conductor
AWG Stranding Nom. Diameter Material
14 Solid 0.064 in BCCS - Bare Copper Covered Steel
Insulation
Material Nom. Diameter
PE - Polyethylene (Foam) 0.280 in
Outer Shield Material
Layer Outer Shield Type Material Material Trade Name Coverage
1 Tape Tri-Laminate (Alum+Poly+Alum) Duobond® II 100%
2 Braid Aluminum 60%
3 Tape Tri-Laminate (Alum+Poly+Alum) Duofoil® 100%
4 Braid Aluminum 40%
Outer Jacket Material
Material Nom. Diameter
PVC - Polyvinyl Chloride 0.407 in
Electrical Characteristics
Return Loss
Frequency [MHz] Min. Structural Return Loss [dB]
5 - 400 MHz 20 dB
Attenuation
Frequency Nom. Attenuation [dB/100ft]
1 MHz 0.16 dB/100ft
2 MHz 0.18 dB/100ft
5 MHz 0.26 dB/100ft
10 MHz 0.38 dB/100ft
20 MHz 0.55 dB/100ft
50 MHz 0.83 dB/100ft
100 MHz 1.17 dB/100ft
200 MHz 1.60 dB/100ft
300 MHz 1.99 dB/100ft
400 MHz 2.30 dB/100ft
Electricals
Nom. Conductor DCR Nom. Outer Shield DCR Nom. Capacitance Cond-to-Shield Nom. Characteristic Impedance Nom. Velocity
11.5 Ohm/1000ft 1.8 Ohm/1000ft 16.3 pF/ft 75 Ohm 83%
Voltage
UL Voltage Rating
300 V (CMR, CMG)
Mechanical Characteristics
Temperature
UL Rating Operating
75°C -30°C to 75°C
Bend Radius
Installation Min.
4 in

Bulk Cable Weight

60 lbs/1000ft

Max. Pull Tension

234 lbs

Standards and Compliance

Environmental Suitability

Indoor - Plenum, Indoor, Outdoor, Sunlight Resistance

Sustainability

CA Prop 65

Flammability / Fire Resistance

UL 1666 Riser

NEC / UL Compliance

CMR, CL2R

CEC / C(UL) Compliance

CMG

European Directive Compliance

EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

APAC Compliance

China RoHS II (GB/T 26572-2011)

Plenum Number

3095A

Product Notes

Notes

Tap marks every 2.6 meters to aid users in installation.

History

Update and Revision

Revision Number: 0.387 Revision Date: 05-26-2021